预应力钢绞线网加固RC柱抗震性能影响因素研究
DOI:
作者:
作者单位:

作者简介:

曹忠民(1972—),男,副教授,研究方向为结构抗震加固。

通讯作者:

中图分类号:

U378.3

基金项目:

国家自然科学基金项目(05168019)


Study on Influencing Factor of Seismic RC Columns Strengthened with Prestressed Steel Wire Mesh and High Performance Mortar
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    基于 8 根试件(其中 1 根未加固试件,7 根为采用预应力钢绞线网加固试件)在低周往复荷载作用下的试验结果,根据对比不同因素下试件的滞回曲线、骨架曲线及延性变化,分析钢绞线间距、预应力水平和轴压比等因素对加固柱抗震性能的影响。 试验结果表明:在预应力水平为 0~60%的范围内,加固柱的屈服荷载、峰值荷载、延性随预应力水平提高均得到提高,提高幅度分别为 4.4%~30.6%,16.4%~60.4%,8.2%~49.8%。 钢绞线间距为 30 mm 的试件较间距为 60 mm 的加固柱,屈服荷载、峰值荷载、延性提高幅度分别为 7.0%~10.9%,17.0%~25.1%,15.1%~35.2%。

    Abstract:

    Based on the experimental result of eight concrete columns (including one unreinforced specimen and seven strengthened specimens with prestressed high strength steel wire mesh) under low cyclic loading, this pa- per, by calculating the hysteretic curve, skeleton curve and ductility change of specimens in terms of different factors, analyzed the effects of such factors as steel strand space, prestressing level and axial compression ratio on the seismic behavior of the strengthened columns. The research results show that within the prestressing level range of 0~60%, with the increase of prestressing level, the yield load, ultimate load, displacement ductility co- efficient of the reinforced concrete columns increased by 4.4%~30.6%, 16.4%~60.4% and 8.2%~49.8%. The yield load, ultimate load ductility coefficient and displacement ductility coefficient of the reinforced specimens with strand spacing of 30mm were 7.0%~10.9%, 17.0%~25.1% and 15.1%~35.2% greater than those of the re- inforced specimens with strand spacing of 60mm respectively.

    参考文献
    相似文献
    引证文献
引用本文

曹忠民,赖恒力,邱荣文,黄金龙.预应力钢绞线网加固RC柱抗震性能影响因素研究[J].华东交通大学学报,2018,35(4):15-20.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2021-05-26
  • 出版日期: