波纹钢板加固钢筋混凝土梁抗弯性能试验与数值分析
DOI:
作者:
作者单位:

1.江西省天驰高速科技发展有限公司,江西 南昌 330103 ;2.华东交通大学土木建筑学院,江西 南昌 330013 ;3.华东交通大学江西省地下空间技术开发工程研究中心,江西 南昌 330013

作者简介:

梁国卿(1983—),男,高级工程师,研究方向为高速公路运营管理。E-mail:184821309@qq.com。

通讯作者:

中图分类号:

TU375.1

基金项目:

江西省重点研发计划项目(20232BBE50014);江西省交通运输厅科技项目(2021H0035);江西省交通运输厅重点工程科技项目(2023C0001)


Experiment and Numerical Study on the Flexural Performance of Concrete Beams Reinforced with Corrugated Steel Plates
Author:
Affiliation:

1.Jiangxi Tianchi Highway Technology Co., Ltd., Nanchang 330103 , China ; 2.School of Civil Engineering and Architecture, EastChina Jiaotong University,Nanchang 330013 , China ; 3.Key Laboratory of Geotechnical Infrastructure Safety and Control ofJiangxi Province, East China JiaotongUniversity, Nanchang 330013 , China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    目的】为研究波纹钢板内衬加固隧道衬砌的局部荷载传递机理和力学性能。【方法】将隧道衬砌单元视作为梁单元,开展了波纹钢板加固钢筋混凝土梁的抗弯性能试验,建立相应的三维精细化有限元模型,通过试验结果验证模型并对荷载传递机理进行分析。【结果】研究结果表明,与未加固的梁相比,波纹钢板加固梁的极限荷载提高了30%~41%,极限荷载随锚栓数量的增加而提高,波纹钢板与混凝土结构的相对滑移随锚栓数量的增加而降低。在加载初期波纹钢板均处于中性层位置,应变基本为零;达到开裂荷载后,波纹钢板波峰整体处于受压状态,而波谷一直处于受拉状态。【结论】通过有限元软件分析,验证了试件破坏模式及波纹钢板荷载-应变情况,模拟结果与试验结果较吻合。

    Abstract:

    Objective】In order to study the local load transfer mechanism and mechanical properties of tunnel lining reinforced with corrugated steel plate lining.【Method】The tunnel lining unit was regarded as a beam unit, and a bending performance test of concrete beam reinforced with corrugated steel plate was carried out. Establish a corresponding three-dimensional refined finite element model, verify the model through test results, and analyze the load transfer mechanism.【Result】Research results show that compared with unreinforced beams, the ultimate load of beams reinforced with corrugated steel plates is increased by 30% to 41%, and the ultimate load increases with the increase in the number of anchor bolts. The relative slip between the corrugated steel plate and the concrete structure decreases as the number of anchor bolts increases. At the initial stage of loading, the corrugated steel plate is in the neutral layer position, and the strain is basically zero; after reaching the cracking load, the entire corrugated steel plate peak is in a compressive state, while the corrugated steel plate trough is always in a tensile state.【Conclusion】Finally, through the finite element software analysis, the failure mode of the specimen and the load-strain of the corrugated steel plate are verified. The simulation results are in good agreement with the experimental results.

    参考文献
    相似文献
    引证文献
引用本文

梁国卿,赵俊宇,毛国辉,朱碧堂.波纹钢板加固钢筋混凝土梁抗弯性能试验与数值分析[J].华东交通大学学报,2024,41(4):36-44.
Liang Guoqing, Zhao Junyu, Mao Guohui, Zhu Bitang. Experiment and Numerical Study on the Flexural Performance of Concrete Beams Reinforced with Corrugated Steel Plates[J]. JOURNAL OF EAST CHINA JIAOTONG UNIVERSTTY,2024,41(4):36-44

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2023-10-16
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2024-09-23
  • 出版日期: